beautypg.com

Developing your project without a communication, Network – Rockwell Automation 9301 Series RSView32 Users Guide User Manual

Page 62

background image

2–22

RSView32 User’s Guide

Developing your project without a communication

network

You can develop your RSView32 project to use direct drivers without
having an Allen–Bradley network or programmable controller. To do
so, use the None Loaded driver type.

1.

Open the Channel editor.

2.

Select a channel and, in the Network Type field, select a network
for the channel.

3.

In the Primary Communication Driver field, click None Loaded.

Using the None Loaded driver type allows you to add or change
tags without causing communication errors.

To set a configured channel’s network type to None Loaded, first
issue the ComStatusOff command. Because setting a configured
channel’s network type to None Loaded deletes all the comstatus
system tags from the tag database, you cannot set a configured
channel’s network type to None Loaded if the ComStatusOn
command has been issued.

4.

Disable the node by clicking the Enabled check box to deselect it.