beautypg.com

Plc–5 timers, counters, and control files – Rockwell Automation 9301 Series RSView32 Users Guide User Manual

Page 705

background image

Addressing syntax for Allen–Bradley programmable controllers

D–7

PLC–5 timers, counters, and control files

Fnnn:eee.MNE/bb

F

File type:
C = Counter
T = Timer
R = Control

nnn

File number: 3 – 999 decimal
For direct driver communication, timer, counter
and control file types use the default file number
if the file number is absent. The default numbers
are 4 (timer), 5 (counter), and 6 (control).

eee

Element number: 0 – 999 decimal

MNE

Member mnemonic (see mnemonic tables
starting on page D-30)

bb

(optional)

Bit number: 0 – 15 decimal
Only applies to analog word members.

Example: T57:38.ACC