Creating graphic displays

11–39

To create a parameter file:

1.

Open the Parameters editor.

2.

Type one entry for each unique placeholder in the display,
associating the placeholder with a tag name. For example:

#1 = bean_weight
#2 = bean_level
#3 = bean_temp

3.

Save the file with a meaningful name (for example, Beans).

For tag placeholders in alarm summary objects in graphic displays
only, you can use wildcards in the parameter file. For example,
#1 = bean_* is a valid parameter entry. The alarm summary would
display any alarms associated with tags beginning with bean_.

Note that you cannot use wildcards in placeholders for any other type
of graphic object.

To run a parameter file:

Type the following command in a macro or anywhere else you can use
an RSView32 command:

Display <file> [/Pfile]

where:

>

is the name of the graphic display file.

[/Pfile]

is the parameter file containing the tags to be
substituted into the display.