Ways to stop derived tag processing

When a project stops, derived tag processing stops as well. To stop
derived tag processing without stopping the project, use any of the
methods below.

In the Graphic Display editor, specify the DerivedOff <file>

command in the Shutdown field in the Display Settings dialog box.
When the display closes derived tag processing stops.

Note that if the display is cached using the Always Updating
option, the DerivedOff command won’t be executed until the
display is removed from the cache (for example, by using the
FlushCache command).

In the Graphic Display editor, create a button object and specify

the DerivedOff <file> command as the press action. When the
button is pressed, derived tag processing stops.

In the Graphic Display editor, create a graphic object and attach

touch animation with the DerivedOff <file> command as the
action. When the object is touched, derived tag processing stops.

In the Events editor, specify the DerivedOff <file> command as

the action for an event.

On the command line, type

DerivedOff <file>

and then press

Enter.