26
Data Entry Key
Selection
S0033
Coil
(1 bit)
Read/
Write
HMC7000
User can choose the mode
of data entry using this bit.
1= Start data entry only
through 'Enter' key.
0= Start data entry through
'Enter' key or Numeric
key.
27
Ladder
Instruction Error
Status
S0034
Coil
(1 bit)
HMC7000
Set if Division by zero
operation is performed in
the ladder instruction and
for invalid conditions or
operands in case of
conversion instructions.
28
Real and
Historical Alarm
Control
S0035
Coil
(1 bit)
Read/
Write
HMC7000
If the selected coil is one
the unit will not monitoring
(Ignoring) any alarm. After
resetting the coil unit will
again start to monitor the
alarm.
29
RUN LED Control
S0036
Coil
(1 bit)
Read/
Write
HMC7000
0: LED functionality works
for
upload/RUN/Communicatio
n status 1: LED OFF
30
USB Host Menu
Trigger
S0037
Coil
(1 bit)
Read/
Write
HMC7035A-M
HMC7057A-M
System tag to allow USB
host operation to user
31
Factory
application Menu
Trigger
S0038
Coil
(1 bit)
Read/
Write
HMC7035A-M
HMC7057A-M
System tag to allow to enter
in Factory application mode
32
Backlight Color
Control-Red
(Retentive)
S0039
Coil
(1 bit)
Read/
Write
HMC7030
models
To control the RED Color
backlight operation
33
Backlight Color
Control-Green
(Retentive)
S0040
Coil
(1 bit)
Read/
Write
HMC7030
models
To control the GREEN Color
backlight operation
34
Backlight Color
Control-Blue
(Retentive)
S0041
Coil
(1 bit)
Read/
Write
HMC7030
models
To control the BLUE Color
backlight operation