beautypg.com

Maple Systems MAPware-7000 User Manual

Page 187

background image

MAPware-7000 Programming Manual

187

1010-1040, Rev. 02

Trend Properties Options

Appearance section – these attributes determine the general look of the trend.

Background Color - determines the fill or background color of the trend graph. Click on
the

button to display the color palette and select a color.

Data Type – options are:

Data Type

Range

Target Address
(2 bytes)

Target Address
(4 bytes)

Unsigned

0 to 65535

0 to 4294967295

Signed

-32768 to 32767

-2147483648 to
2147483647

Hexadecimal

0000 to FFFF

0000 to FFFFFFFF

BCD

1

0 to 9999

0 to 99999999

Floating Point

2

NA

Maximum of 9 digits

1- If the value in the monitored target register is not a valid BCD number, a dollar sign

‘$’ is displayed.

2- Floating Point format is based upon the IEEE 754 standard for 32-bit single precision

numbers. A maximum of nine digits is supported. Values are rounded to the
nearest decimal point (ex: if Format: Digits After Decimal Point is set to 1 digit, then
floating point number 1.52 would be displayed as 1.5 and 1.56 would be displayed
as 1.6) shows the current state displayed on the Multiple Bar Graphs for editing

Error Message Font Color – determines the color of any error messages that may appear
during the execution of the trend graph. Click on the

button to display the color

palette and select a color.

Font – used to configure the pixel size (WxH) of the error message. Options are 5x7 and
7x14 pixels. Note: error messages that do appear display along the bottom of the trend
graph.

Grid – option to display grid lines on the trend graph

Grid Color – determines the color of the grid lines. Click on the

button to display the

color palette and select a color.

Label – option to have a text label appear on the top of the trend.

o Label Font – determines the font type, size, etc.

 Name- Type font used
 Size- select font size
Bold- select ‘True’ to enable
Italic- select ‘True’ to enable
 Underline- select ‘True’ to enable

o Label Text – enter the text to appear in the label.
o Label Text Color – determines the text color of the label. Click on the

button

to display the color palette and select a color.

Language – highlight the language that must be selected to display the entered text.

Span – options are Time (sec) or Tag Selected. Select Time (sec) to configure a pre-
defined length of time (in seconds) for the values plotted on the trend graph. Use Tag
Selected to configure a PLC target address continuously read by the HMC to determine
the length of time used by the trend graph.