Writing the date/time, Internal battery – Maple Systems MAPware-7000 User Manual
Page 275
MAPware-7000 Programming Manual
275
1010-1040, Rev. 02
With 1=Sun…7=Sat
5
Minute Change
Status
S00003
Momentarily sets whenever
the minute value in SW14
changes
Read Only
6
Hour Change
Status
S00004
Momentarily sets when the
hour value in SW13 changes
Read Only
7
Date Change Status S00005
Momentarily sets when the
date value in SW10 changes
Read Only
8
Month Change
Status
S00006
Momentarily sets when the
month value in SW11
changes
Read Only
9
Year Change Status S00007
Momentarily sets when the
year value in SW12 changes
Read Only
12
RTC battery status
S00010
Sets when battery is dead
Read Only
17
Invalid RTC date
entry
S00019
Sets while an invalid value is
in one of the RTC registers
Read Only
36
RTC Status
SW0003_02
Sets if the RTC is not working Read Only
Writing the Date/Time
You can set or change the internal RTC using several means:
By entering the local setup menus (see Appendix C – Maintenance and Test Modes)
By using the Set RTC task for a function key or one of the multi-task buttons (see
Chapter 6 – Task Management)
By using the Set Calendar (CLND) instruction in the ladder logic commands (see The
HMC7000 Series Ladder Logic Instructions Manual)
You cannot directly write to the clock using the SW10-16 internal system registers. However, if
you wish to write directly, simply use the Numeric Entry object with data registers that are
referenced in the Set Calendar instruction in a ladder logic program.
Internal Battery
The internal battery is used to power the real-time clock (RTC) when the HMC is not powered by
external 24VDC. Normally, the internal battery should be able to provide power to the RTC for
approximately 20 years (@25°C).