beautypg.com

Maple Systems MAPware-7000 User Manual

Page 305

background image

MAPware-7000 Programming Manual

305

1010-1040, Rev. 02

14

Invalid key
beeper Control

S0017

Coil
(1 bit)

Read/
Write

HMC7035A-M
HMC7057A-M

1: Enable Invalid beeper; 0:
Disable Invalid beeper. Run
time you can change this bit

15

Invalid RTC date
entry

S0019

Coil
(1 bit)

Read
only

HMC7000

0=valid date; 1= Invalid date

16

Popup Screen
trigger

S0020

Coil
(1 bit)

Read/
Write

HMC7035A-M
HMC7057A-M

This bit triggers the popup
screen number stored in
SW23

17

COM1 failed
node reconnect
control

S0021

Coil
(1 bit)

Read/
write

HMC7000

If this bit is set
communication with the
failed nodes is detected
after scan time SW0018 for
port1. By default : ON

18

COM2 failed
node reconnect
control

S0022

Coil
(1 bit)

Read/
write

HMC7057A-M

If this bit is set
communication with the
failed nodes is detected
after scan time SW0019 for
port2. By default : ON

19

COM3 failed
node reconnect
control

S0023

Coil
(1 bit)

Read/
write

PLC7008A-ME
only

If this bit is set
communication with the
failed nodes is detected
after scan time SW0022 for
port3. By default : ON

20

Static Data Entry
Focus Control

S0027

Coil
(1 bit)

Read/
Write

HMC7030A-M
only

User can enable focus for
static data entry using this
bit.

21

Datlog Group1
log Control

S0028

Coil
(1 bit)

Read/
Write

HMC7035A-M
HMC7057A-M

User can Start/Stop logging
in Bit Task mode for Group1
by using this bit

22

Datlog Group2
log Control

S0029

Coil
(1 bit)

Read/
Write

HMC7035A-M
HMC7057A-M

User can Start/Stop logging
in Bit Task mode for Group2
by using this bit

23

Datlog Group3
log Control

S0030

Coil
(1 bit)

Read/
Write

HMC7035A-M
HMC7057A-M

User can Start/Stop logging
in Bit Task mode for Group3
by using this bit

24

Datlog Group4
log Control

S0031

Coil
(1 bit)

Read/
Write

HMC7035A-M
HMC7057A-M

User can Start/Stop logging
in Bit Task mode for Group4
by using this bit

25

Data Entry Lock
Control

S0032

Coil
(1 bit)

Read/
Write

HMC7000

User can Lock / Unlock the
data entry. 1= Data_Entry
Lock, 0= Data_Entry
unlock.