5motor control (mctrl) – Lenze 8400 motec User Manual
Page 89
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
89
5
Motor control (MCTRL)
5.2
Motor selection/Motor data
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
How to carry out automatic motor parameter identification:
1. Inhibit the controller if it is enabled, e.g. via the
device command or a LOW
signal at the RFR terminal.
2. Wait until the drive is at standstill.
3. Transfer the nameplate data to the following codes:
•
: Rated motor power
•
: Rated motor speed
•
: Rated motor current (according to the connection method /)
•
: Rated motor frequency (according to the connection method /)
•
: Rated motor voltage (according to the connection method /)
•
: Motor cos ϕ
4. Start motor parameter identification via the
device command.
5. Enable the controller again.
• Motor parameter identification starts.
• The motor parameter identification takes approx. 30 s.
• The identification is completed if the "0: Off / ready" message is displayed in
6. Inhibit controller again.
Note!
Motor parameter identification may be aborted by the controller if a special motor (e.g.
mid-frequency motor) is used or if there is a large deviation between inverter and motor
power.
Another cause for the abort of the motor parameter identification could be the
implausibility of the entered nameplate data, e.g. the entry P = 0 kW for the motor
power.