Ce2: can rpdo2 [xx.0135.00002, Ci01: module missing/incompatible [xx.0140.00013, Ps01: no memory module [xx.0144.00001 – Lenze 8400 motec User Manual
Page 312: Ps02: par. set invalid [xx.0144.00002, Ps03: par. set device invalid [xx.0144.00003, Xx.0135.00002, Xx.0140.00013, Xx.0144.00001, Xx.0144.00002, Xx.0144.00003
![background image](/manuals/566305/312/background.png)
9
Diagnostics & error management
9.8
Error messages of the operating system
312
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CE2: CAN RPDO2 [xx.0135.00002]
CI01: Module missing/incompatible [xx.0140.00013]
PS01: No memory module [xx.0144.00001]
PS02: Par. set invalid [xx.0144.00002]
PS03: Par. set device invalid [xx.0144.00003]
Response (Lenze setting printed in bold)
Setting:
C00593/2
( Adjustable response)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
CAN interface: Time monitoring for RPDO2 has tripped.
• RPDO2 has not been received within the monitoring
time set in C00357/2 or was faulty.
• Set correct telegram length for CAN master (transmit-
ter).
• Eliminate electrical interference (e.g. EMC).
• Adjust monitoring time C00357/2 or switch off time
monitoring.
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
There is a connection problem between the communica-
tion unit and the drive unit or an incompatibility.
• Check installation of the 8400 motec.
• In case of an incompatibility, either the communica-
tion unit or the software of the drive unit is out of
date. In this case, please contact Lenze.
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
Memory module is either not available or not snapped
into place correctly.
• If a memory module has been provided: Plug the
memory module into the slot of the drive unit intend-
ed for this purpose.
• If a memory module has been provided: Check if the
memory module has been plugged-in correctly.
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
The parameter set stored in the memory module is
invalid. The reason for this can be as follows:
• Incomplete storage of the parameter set due to volt-
age failure.
• The plugged-in memory module stems from a device
with more recent firmware (compare
) or from
a different device type (e.g. 8400 BaseLine).
The error can only be eliminated by loading the Lenze
setting with the device command
= "1: On /
start".
• In order to prevent the error, do not switch off the
voltage during the saving process.
• If the parameter set is to be transferred from one de-
vice with a higher version to a device with a lower ver-
sion, use the "copy parameter set" function of the
keypad. Make sure that you do not use functions that
are not available in the older device.
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
The parameter set in the device is invalid.
Consultation with Lenze required.