C00064
C00066
C00070
Parameter | Name:
C00064 | Device utilisation (Ixt)
Data type: INTEGER_16
Index: 24511
d
= 5FBF
h
Display of the device utilisation Ixt in different time resolutions
• If the value displayed here exceeds the threshold set in
, the fault message "OC5: Device overload (Ixt)"
is output and the fault response set in
is executed (default setting: "Warning").
Display range
(min. value | unit | max. value)
0
%
250
Subcodes
Info
C00064/1
Device utilisation (Ixt)
• Maximum value of the pulse utilisation (C00064/2)
and permanent utilisation (C00064/3).
C00064/2
Device utilisation (Ixt) 15s
• Pulse utilisation over the last 15 seconds (only for
loads >160 %).
C00064/3
Device utilisation (Ixt) 3 min
• Permanent utilisation over the last 3 minutes.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00066 | Thermal motor load (I²xt)
Data type: INTEGER_16
Index: 24509
d
= 5FBD
h
Display of the thermal motor load, sensorlessly determined using a motor model
• If the value displayed here exceeds "100.00 %", the error message "OC6: Thermal motor overload (I2xt)" is output
is executed (default setting: "Warning").
Motor overload monitoring (I2xt)
Display range
(min. value | unit | max. value)
0
%
200
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00070 | Vp speed controller
Data type: UNSIGNED_16
Index: 24505
d
= 5FB9
h
From version 03.00.00
Gain factor Vp of the speed controller for sensorless control for synchronous motors (
Setting range
(min. value | unit | max. value)
0.00
600.00
Subcodes
Lenze setting
Info
C00070/1
0.00
Reserved
C00070/2
0.00
Reserved
C00070/3
3.00
: Vp speed controller
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100