1 adapting the v/f base frequency, Adapting the v/f base frequency, Adapting the v/f base frequency ( 101) – Lenze 8400 motec User Manual
Page 101: 5motor control (mctrl)
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
101
5
Motor control (MCTRL)
5.5
V/f characteristic control (VFCplus)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.5.3.1
Adapting the V/f base frequency
The V/f base frequency (
) determines the slope of the V/f characteristic and has
considerable influence on the current, torque, and power performance of the motor.
applies to all permitted mains voltages.
• Mains fluctuations or fluctuations of the DC-bus voltage (operation in generator mode) do not
need to be considered when the V/f base frequency is set. They are automatically compensated
for by the internal mains voltage compensation of the device.
• Depending on the setting in
, it may be required to adapt the reference speed (
)
to traverse the entire speed range of the motor.
• As a typical value, the V/f base frequency (
) is set to the value of the rated motor
frequency (
) for standard applications and corresponds to the data on the motor
nameplate.
• Reference voltage for the V/f base frequency is the rated motor voltage (
) according to
the motor nameplate.
Note!
87-Hz operation
4-pole asynchronous motors which are designed for a rated frequency of f = 50 Hz in star
connection can be operated in delta connection when being constantly excited up to f =
87 Hz.
• Advantages:
• Higher speed-setting range
• 73% higher power output in case of standard motors
• Motor current and motor power increase by the factor
.
• The field weakening range starts above 87 Hz.
• Generally, this process can also be used with motors which have different numbers of
pole pairs. In case of 2-pole asynchronous motors, the mechanical limit speed must be
maintained.
3