Technology applications
7.2
TA "Actuating drive speed"
204
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Selection of the main speed setpoint
The main speed setpoint is selected in the Lenze setting via the analog input 1.
• Scaling: 10 V ≡ 100 % reference speed (
• The main setpoint is transformed to a speed setpoint in the setpoint encoder via a ramp
function generator with linear or S-shaped ramps.
• For a detailed functional description see FB
.
Motor potentiometer function
Alternatively, the main speed setpoint can be generated via a motor potentiometer function.
• In the Lenze setting, the motor potentiometer function is deactivated.
• Activation is possible via
or via the bMPotEnable input.
• The behaviour of the motor potentiometer during switch-on of the drive system can be selected
in
.
• For a detailed functional description see FB
Process controller
A process controller (PID controller) is connected downstream of the setpoint generator.
• In the Lenze setting, the process controller is deactivated.
• The activation is executed by selecting the operating mode in
.
• For a detailed functional description see FB
.
nAdapt_a
)
in percent
nAct_a
)
Speed or actual sensor value (actual process value)
nInflu_a
)
Limitation of the influencing factor in percent
Speed setpoint
Speed setpoint
Parameter
Info