3commissioning – Lenze 8400 motec User Manual
Page 38

3
Commissioning
3.5
Commissioning of the "Actuating drive speed" technology application
38
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Tip!
Also check the other information on the nameplate against the motor data set in the drive
controller. You can find further information in the chapter entitled "
".
Recommendations for the following application cases:
• If the controller and motor differ greatly from each other in terms of performance:
Set the Imax limit (in motor mode) in
to double the rated motor current.
• If a higher starting torque is required:
In idle state of the motor, set the Vmin boost in
in such a way that the rated
motor current flows at a field frequency of f = 3 Hz (display in
• If a high torque must be provided at small speeds without feedback:
Select "Sensorless vector control (SLVC) as motor control mode in
Related topics:
V/f characteristic control (VFCplus)
Sensorless vector control (SLVC)