C00050 | mctrl: speed setpoint, C00051 | mctrl: actual speed value, C00052 | motor voltage – Lenze 8400 motec User Manual
Page 342: C00053 | dc-bus voltage, C00054 | motor current, C00051, C00053, C00054, C00052, C00050

11
Parameter reference
11.2
Parameter list | C00050
342
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00050
C00051
C00052
C00053
C00054
Parameter | Name:
C00050 | MCTRL: Speed setpoint
Data type: INTEGER_32
Index: 24525
d
= 5FCD
h
Display of the speed setpoint at the speed setpoint input of the motor control
Display range
(min. value | unit | max. value)
-9999
rpm
9999
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00051 | MCTRL: Actual speed value
Data type: INTEGER_32
Index: 24524
d
= 5FCC
h
Display of the actual speed value of the motor shaft
Note:
The displayed value only corresponds to the real actual speed value of the motor shaft if an encoder is connected to
the motor and the evaluation of the feedback signal has been set correctly ("Closed loop" operation).
In case of operation without speed feedback, the signal is calculated from the motor control and thus may not
correspond to the real actual speed.
Display range
(min. value | unit | max. value)
-9999
rpm
9999
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00052 | Motor voltage
Data type: UNSIGNED_16
Index: 24523
d
= 5FCB
h
Display of the current motor voltage/output voltage of the inverter
Display range
(min. value | unit | max. value)
0
V
1000
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00053 | DC-bus voltage
Data type: UNSIGNED_16
Index: 24522
d
= 5FCA
h
Display of the current DC-bus voltage
Display range
(min. value | unit | max. value)
0
V
1000
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00054 | Motor current
Data type: UNSIGNED_16
Index: 24521
d
= 5FC9
h
Display of the current motor current/output current of the inverter
Display range
(min. value | unit | max. value)
0.00
A
300.00
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100