Diagnostics & error management
9.6
Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.6.2
Setting the error response
When a monitoring function responds, the response set for this monitoring function (Trouble, Fault,
etc.) will be triggered.
• For many monitoring functions the response can be individually parameterised via parameters.
Tip!
The table in the chapter entitled "
" contains the error messages for
which the response can be set.
Warning thresholds
Some of the monitoring functions are activated if a defined warning threshold has been exceeded.
• The corresponding preset threshold values can be changed via the following parameters:
Parameter
Info
Lenze setting
Value Unit
Motor overload threshold (I²xt)
100 %
Device utilisat. threshold (Ixt)
100 %
Max. positive speed
120 %
Max. negative speed
120 %
Max. positive output frequency
300 Hz
Max. negative output frequency
300 Hz