Ps04: par. set device incompatible [xx.0144.00004, Ps31: ident. error [xx.0144.00031, Df01: internal error 01 [xx.0145.00001 – Lenze 8400 motec User Manual
Page 313: Df02: internal error 02 [xx.0145.00002, Df03: internal error 03 [xx.0145.00003, Xx.0145.00001, Xx.0145.00002, Xx.0145.00003, Xx.0144.00004, Xx.0144.00031
![background image](/manuals/566305/313/background.png)
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
313
9
Diagnostics & error management
9.8
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PS04: Par. set device incompatible [xx.0144.00004]
PS31: Ident. error [xx.0144.00031]
dF01: Internal error 01 [xx.0145.00001]
dF02: Internal error 02 [xx.0145.00002]
dF03: Internal error 03 [xx.0145.00003]
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
The parameter set saved to the memory module is in-
compatible to the standard device.
• Incompatibility of the parameter set is e.g. caused if
the parameter set in the memory module has a higher
version than the standard device.
When the memory modules are exchanged, observe the
downward compatibility:
• OK: motec V1.0 to motec > V1.0
• Not OK: motec V2.0 to motec < V2.0
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
Incompatible or unknown HW components have been
found.
• Check which HW components are faulty (
Product type code).
• Check connection between communication unit and
drive unit regarding for contact problems.
• Check temperature range of the device at the start.
• Replace communication unit.
• Check whether a software update at Lenze is possible.
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
Device error
• Reduce switching frequency (
) to 4 kHz.
• Please contact Lenze if the problem occurs again.
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
Device error
• Mains switching or restart of the controller, respec-
tively.
• Please contact Lenze if the problem occurs again.
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
Device error
• Mains switching or restart of the controller, respec-
tively.
• Please contact Lenze if the problem occurs again.