Diagnostics & error management
9.8
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
oH3: Motor temperature triggered [xx.0119.00015]
oC5: Ixt overload [xx.0119.00050]
oC9: Ixt overload - shutdown limit [xx.0119.00052]
oC7: Motor overcurrent [xx.0123.00007]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
The motor temperature monitoring mode at plug X??
has triggered.
Possible causes:
• The motor is overheated so that the thermal contact
integrated into the motor has been switched.
• An open circuit or a loose contact at the connections
mentioned above has occurred.
• Check motor temperature monitoring.
• Provide for sufficient cooling of the motor.
• Check terminals for open circuit or loose contact.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
The Ixt overload check has tripped.
• Operating threshold = 100 % Ixt (adjustable in
Possible causes:
• Wrong dimensioning of the device with regard to its
motor load.
• Load cycles are not complied with.
• Check and, if required, correct dimensioning of the
device and the motor load with regard to technical
data.
• Reduce motor load cycles (observe load cycles accord-
ing to documentation).
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
The Ixt overload check has tripped.
• Operating threshold = 110 % Ixt (fixed)
Possible causes:
• Wrong dimensioning of the device with regard to its
motor load.
• Load cycles are not complied with.
• Check and, if required, correct dimensioning of the
device and the motor load with regard to technical
data.
• Reduce motor load cycles (observe load cycles accord-
ing to documentation).
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
Maximum current monitoring has tripped.
Check and, if required, correct dimensioning of the load
with regard to the installed device power.