Device control (DCTRL)
4.1
Device commands (C00002/x)
62
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.1.1
Load Lenze setting
The
= "1: On / start" device command resets the parameters to the Lenze setting which
are saved in the controller Firmware.
• Can only be executed if the controller is inhibited; otherwise, the feedback
= "6: No
access - controller inhibit" will be returned.
• All parameter changes made since the last saving of the parameter set will get lost!
• This device command has an effect on the settings of the parameters of the operating system,
application and module.
How to load the Lenze setting:
1. If the controller is enabled, it must be inhibited, e.g. by executing the "Enable/Inhibit con-
troller" device command (
= "0: Off / ready").
2. Execute the "Load Lenze setting" device command:
= "1: On / start"
The load process may take a couple of seconds. After the device command has been called
, a dynamic status information ("Work in progress" "Off / Ready") is re-
turned.