C00976 | vfc-eco: ti, C00977 | vfc-eco: minimum voltage v/f, C00978 | vfc-eco: motor voltage sub – Lenze 8400 motec User Manual
Page 406: C00979 | cosine phi, C00980 | output power, C00976, C00977, C00978, C00980/1, C00980/2

11
Parameter reference
11.2
Parameter list | C00976
406
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00976
C00977
C00978
C00979
C00980
Parameter | Name:
C00976 | VFC-ECO: Ti
Data type: UNSIGNED_16
Index: 23599
d
= 5C2F
h
Reset time of the Cos-Phi controller for energy-saving V/f characteristic control (
)
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
ms
6000.0 200.0 ms
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00977 | VFC-ECO: Minimum voltage V/f
Data type: UNSIGNED_8
Index: 23598
d
= 5C2E
h
Minimum voltage V/f of the Cos-Phi controller for energy-saving V/f characteristic control (
Setting range
(min. value | unit | max. value)
Lenze setting
20
%
100 20 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00978 | VFC-ECO: Motor voltage sub
Data type: INTEGER_16
Index: 23597
d
= 5C2D
h
Display of the voltage reduction with energy-saving V/f characteristic control (
Display range
(min. value | unit | max. value)
-1000
V
1000
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00979 | Cosine phi
Data type: INTEGER_16
Index: 23596
d
= 5C2C
h
Display of the cosϕ setpoint and actual value with energy-saving V/f characteristic control (
)
Display range
(min. value | unit | max. value)
-1.00
1.00
Subcodes
Info
C00979/1
Cosine phi act
C00979/2
Cosine phi set
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00980 | Output power
Data type: INTEGER_32
Index: 23595
d
= 5C2B
h
Display parameter for an energy analysis in the prevailing application. From this, decisions can be deduced whether
a measure for energy optimisation is economic.
Display range
(min. value | unit | max. value)
0.000
kW
32.000
Subcodes
Info
C00980/1
Active output power
C00980/2
Apparent output power
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000