C00517 | user menu, C00565 | resp. to mains phase failure, C00517 – Lenze 8400 motec User Manual
Page 382: C00565, 11 parameter reference
11
Parameter reference
11.2
Parameter list | C00517
382
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00517
C00565
Parameter | Name:
C00517 | User menu
Data type: INTEGER_32
Index: 24058
d
= 5DFA
h
When a system is installed, parameters must be changed time and again until the system runs satisfactorily. The
user menu of a device serves to create a selection of frequently used parameters to be able to access and change
these parameters quickly.
• Format: ,
• If "0.000" is set, no entry will be displayed in the user menu.
Setting range
(min. value | unit | max. value)
0.000
16000.000
Subcodes
Lenze setting
Info
C00517/1
51.000
: Display of actual speed value
C00517/2
53.000
: Display of DC-bus voltage
C00517/3
54.000
: Display of motor current
C00517/4
61.000
: Display of heatsink temperature
C00517/5
137.000
: Display of device status
C00517/6
166.003
: Display of current error message
C00517/7
0.000
User menu: Entry 7
C00517/8
11.000
: Reference speed
C00517/9
39.001
: Festsollwert 1
C00517/10
39.002
: Festsollwert 2
C00517/11
12.000
: Accel. time - main setpoint
C00517/12
13.000
C00517/13
15.000
: V/f base frequency
C00517/14
16.000
: Vmin boost
C00517/15
22.000
: Imax in motor mode
C00517/16
120.000
: Setting of motor overload (I
2
xt)
C00517/17
87.000
: Rated motor speed
C00517/18
99.000
: Display of firmware version
C00517/19
200.000
: Display of firmware product type
C00517/20
0.000
User menu: Entry 20
C00517/21
0.000
User menu: Entry 21
C00517/22
0.000
User menu: Entry 22
C00517/23
0.000
User menu: Entry 23
C00517/24
105.000
C00517/25
173.000
: Mains voltage
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000
Parameter | Name:
C00565 | Resp. to mains phase failure
Data type: UNSIGNED_8
Index: 24010
d
= 5DCA
h
Response to the failure of mains phases
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
4 WarningLocked
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1