C00517

C00565

Parameter | Name:

C00517 | User menu

Data type: INTEGER_32

Index: 24058

d

= 5DFA

h

When a system is installed, parameters must be changed time and again until the system runs satisfactorily. The

user menu of a device serves to create a selection of frequently used parameters to be able to access and change

these parameters quickly.

• Format: ,

• If "0.000" is set, no entry will be displayed in the user menu.

Setting range

(min. value | unit | max. value)

0.000

16000.000

Subcodes

Lenze setting

Info

C00517/1

51.000

C00051

: Display of actual speed value

C00517/2

53.000

C00053

: Display of DC-bus voltage

C00517/3

54.000

C00054

: Display of motor current

C00517/4

61.000

C00061

: Display of heatsink temperature

C00517/5

137.000

C00137

: Display of device status

C00517/6

166.003

C00166/3

: Display of current error message

C00517/7

0.000

User menu: Entry 7

C00517/8

11.000

C00011

: Reference speed

C00517/9

39.001

C00039/1

: Festsollwert 1

C00517/10

39.002

C00039/2

: Festsollwert 2

C00517/11

12.000

C00012

: Accel. time - main setpoint

C00517/12

13.000

C00013

: Decel. time - main setpoint

C00517/13

15.000

C00015

: V/f base frequency

C00517/14

16.000

C00016

: Vmin boost

C00517/15

22.000

C00022

: Imax in motor mode

C00517/16

120.000

C00120

: Setting of motor overload (I

2

xt)

C00517/17

87.000

C00087

: Rated motor speed

C00517/18

99.000

C00099

: Display of firmware version

C00517/19

200.000

C00200

: Display of firmware product type

C00517/20

0.000

User menu: Entry 20

C00517/21

0.000

User menu: Entry 21

C00517/22

0.000

User menu: Entry 22

C00517/23

0.000

User menu: Entry 23

C00517/24

105.000

C00105

: Decel. time - quick stop

C00517/25

173.000

C00173

: Mains voltage

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00565 | Resp. to mains phase failure

Data type: UNSIGNED_8

Index: 24010

d

= 5DCA

h

Response to the failure of mains phases
Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
4 WarningLocked

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1