C00803 | l_mpot_1: deceleration time, C00804 | l_mpot_1: inactive fct, C00805 | l_mpot_1: init fct – Lenze 8400 motec User Manual
Page 397: C00806 | l_mpot_1: use, C00806, Or via, C00805, Or via th, T in, C00803
![background image](/manuals/566305/397/background.png)
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
397
11
Parameter reference
11.2
Parameter list | C00803
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00803
C00804
C00805
C00806
Parameter | Name:
C00803 | L_MPot_1: Deceleration time
Data type: UNSIGNED_16
Index: 23772
d
= 5CDC
h
FB: Deceleration time of the motor potentiometer function
Setting range
(min. value | unit | max. value)
Lenze setting
0.1
s
999.9 10.0 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00804 | L_MPot_1: Inactive fct.
Data type: UNSIGNED_8
Index: 23771
d
= 5CDB
h
FB: Selection of the response if the motor potentiometer is deactivated via input bInAct
Selection list
(Lenze setting printed in bold)
Info
0 Retain value
Keep output value
1 Deceleration to 0
Deceleration via ramp to 0
2 Deceleration to lower limit
Deceleration via ramp to the lower limit (
)
3 Without ramp to 0
Step change to 0
4 Without ramp to lower limit
Jump to lower limit (
5 Acceleration to upper limit
Acceleration via ramp to upper limit (
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00805 | L_MPot_1: Init fct.
Data type: UNSIGNED_8
Index: 23770
d
= 5CDA
h
FB: Selection of the response at device switch-on
Selection list
(Lenze setting printed in bold)
0 Load last value
1 Load lower limit
2 Load 0
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00806 | L_MPot_1: Use
Data type: UNSIGNED_8
Index: 23769
d
= 5CD9
h
FB: Use of the motor potentiometer
Selection list
(Lenze setting printed in bold)
Info
0 No
The motor potentiometer is not used.
• The analog value applied to the nIn_a input is looped
through without any changes to the nOut_a output.
1 Yes
The motor potentiometer is used.
• The analog value applied at the nIn_a input is led via
the motor potentiometer and provided at the nOut_a
output.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1