12 function library – Lenze 8400 motec User Manual
Page 499

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
499
12
Function library
12.27
LS_ParReadWrite_1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter
bFail
BOOL
"Error" status
TRUE An error has occurred (group signal).
• See display parameter C01092/1 for details.
wOutHWord
wOutLWord
WORD
Value which was read (DataHigh/DataLow portion) after read request
Parameter
Possible settings
Info
0,000
16000,000 Parameter to be read or written.
• For a setting of "0,000", inputs
wParIndex and wParSubindex are
effective for addressing purposes
instead.
• Lenze setting: 0.000
Format:
,
Cycle time
• Lenze setting: 0
0 One-time reading/writing at
bExecute in case of a FALSE/TRUE
edge
Cyclic reading/writing:
20 20 ms
50 50 ms
100 100 ms
200 200 ms
500 500 ms
1000 1 s
2000 2 s
5000 5 s
10000 10 s
Error status
• If bFail = TRUE:
Error status is displayed.
0 No error
33803 Invalid data type (e.g. STRING)
33804 Limit violation
33806 Invalid code
33813 No element in the selection list
33815 Writing of the parameter not
permitted
33816 Writing of the parameter only
permitted if controller is inhibited
33829 Invalid subcode
33865 No parameter with subcodes
Identifier
Data type
Value/meaning