C00820 | l_digitallogic_1: function, C00821 | l_digitallogic_1: truth table, C00822 | l_digitallogic_2: function – Lenze 8400 motec User Manual
Page 398: 11 parameter reference
![background image](/manuals/566305/398/background.png)
11
Parameter reference
11.2
Parameter list | C00820
398
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00820
C00821
C00822
Parameter | Name:
C00820 | L_DigitalLogic_1: Function
Data type: UNSIGNED_8
Index: 23755
d
= 5CCB
h
From version 02.00.00
FB: Selection of the internal logic function
Selection list
(Lenze setting printed in bold)
Info
0 bOut = 0
Constant value "FALSE"
1 bOut = 1
Constant value "TRUE"
2 bOut = bIn1 AND bIn2
AND operation
3 bOut = bIn1 OR bIn2
OR operation
4 bOut = f (truth table)
The truth table parameterised in
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00821 | L_DigitalLogic_1: Truth table
Data type: UNSIGNED_8
Index: 23754
d
= 5CCA
h
From version 02.00.00
FB: Parameterisation of the truth table
Selection list
0 False
1 True
Subcodes
Lenze setting
Info
C00821/1
0: FALSE
bIn1=0/bIn2=0
C00821/2
0: FALSE
bIn1=1/bIn2=0
C00821/3
0: FALSE
bIn1=0/bIn2=1
C00821/4
0: FALSE
bIn1=1/bIn2=1
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00822 | L_DigitalLogic_2: Function
Data type: UNSIGNED_8
Index: 23753
d
= 5CC9
h
From version 04.00.00
FB: Selection of the internal logic function
Selection list
(Lenze setting printed in bold)
Info
0 bOut = 0
Constant value "FALSE"
1 bOut = 1
Constant value "TRUE"
2 bOut = bIn1 AND ... bIn3
AND operation
3 bOut = bIn1 OR ... bIn3
OR operation
4 bOut = f (truth table)
The truth table parameterised in
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1