C00581 | resp. to ls_seterror_x, C00585 | resp. to motor overtemp. ptc, C00585 – Lenze 8400 motec User Manual
Page 384: Is activated, Fault"), mo, C00582, C00581/1, C00581/2, 11 parameter reference

11
Parameter reference
11.2
Parameter list | C00581
384
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00581
C00582
C00585
Parameter | Name:
C00581 | Resp. to LS_SetError_x
Data type: UNSIGNED_8
Index: 23994
d
= 5DBA
h
Selection of the error responses for application error messages
• An application error message is tripped by a FALSE-TRUE edge at the binary inputs bSetError1...2.
Selection list
0 No Reaction
1 Fault
2 Trouble
4 WarningLocked
Subcodes
Lenze setting
Info
C00581/1
1: Fault
: Resp. to bSetError1
C00581/2
1: Fault
: Resp. to bSetError2
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00582 | Resp. to heatsink temp. > shutdown temp. -5°C
Data type: UNSIGNED_8
Index: 23993
d
= 5DB9
h
Response if the heatsink temperature has reached the switch-off temperature threshold.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
4 WarningLocked
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00585 | Resp. to motor overtemp. PTC
Data type: UNSIGNED_8
Index: 23990
d
= 5DB6
h
Response to motor overtemperature
• The motor temperature is measured by means of a PTC thermistor detector.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
4 WarningLocked
Read access Write access CINH PLC STOP No transfer COM MOT