Smr4: sdo access failure [xx.0127.00006, Ce0f: mci control word [xx.0127.00015, Ce4: can bus off [xx.0131.00000 – Lenze 8400 motec User Manual
Page 310: Ca06: can crc error [xx.0131.00002, Xx.0131.00002, Xx.0127.00015, Xx.0131.00000, Xx.0127.00005, Xx.0127.00006, 9diagnostics & error management

9
Diagnostics & error management
9.8
Error messages of the operating system
310
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Smr3: Module timeout - one or more of PDOs timeout [xx.0127.00005]
Smr4: SDO access failure [xx.0127.00006]
CE0F: MCI control word [xx.0127.00015]
CE4: CAN bus off [xx.0131.00000]
CA06: CAN CRC error [xx.0131.00002]
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
Communication Unit: A timeout has occurred for one or
several PDOs
• Increase timeout in
• Mains switching or restart of the controller, respec-
tively.
• Check correct identification of the Communication
Unit in
• Replace Communication Unit.
• Please contact Lenze if the problem occurs again.
Response (Lenze setting printed in bold)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
An error has occurred during SDO access
• Mains switching or restart of the controller, respec-
tively.
• Please contact Lenze if the problem occurs again.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
Bit 14 ("SetFail") of the wMciCtrl control word of the
system block has been set.
Trace back signal source on the bus (e.g. PROFIBUS) that
sets bit 14 ("SetFail").
Response (Lenze setting printed in bold)
Setting:
C00592/2
( Adjustable response)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
CAN interface: "Bus-Off" state
• Received too many faulty telegrams.
• Damaged cable (e.g. loose contact).
• Two nodes with the same ID.
• Check wiring and bus terminating resistor.
• Set identical baud rate for each bus node.
• Assign different IDs to nodes.
• Eliminate electrical interference (e.g. EMC).
Response (Lenze setting printed in bold)
Setting:
C00592/1
( Adjustable response)
No Reaction Fault Trouble WarningLocked
Cause
Remedy
CAN interface: a faulty CAN telegram has been detected.
• Check wiring and bus terminating resistor.