Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

103

5

Motor control (MCTRL)

5.5

V/f characteristic control (VFCplus)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.5.3.3

Optimising the Imax controller

Using the Lenze setting of the current limitation controller, the drive is stable:

Most applications do not require optimisation.
The setting of the current limitation controller must be adapted if

• power control including great moments of inertia is performed.

• Recommendation: Increase of the reset time Ti (

C00074

) of the I

max

controller.

• vibrations occur in the V/f control (VFCplus + encoder) mode during the intervention of the

current limitation controller.

• Recommendation: Increase of the reset time Ti (

C00074

) of the I

max

controller.

• overcurrent errors occur due to load impulses or too high acceleration ramps.

• Recommendation: Reduction of the gain Vp (

C00073

) and reset time Ti (

C00074

) of the I

max

controller

Parameter

Info

Lenze setting

Value Unit

C00073

VFC: Vp Imax controller

0.25

C00074

VFC: Ti Imax controller

65 ms