7technology applications – Lenze 8400 motec User Manual
Page 232
7
Technology applications
7.3
TA "Actuating drive speed (AC Drive Profile)"
232
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.3.2
Scaling of the speed and torque values (Ref from Net)
Scaling of the speed values
On the bus side, the speed setpoint is defined in [rpm]. In the controller, however, all speed-related
signals are processed in percentage with regard to a reference variable (
). For the scaling
required in this case, the
system bus is used (see also
).
• The type of conversion can be adapted in
.
• A conversion of [rpm] to [%] is preset for the "AC Drive Profile" application according to the
following formula.
• Optionally, an additional scaling can be executed via a scaling factor adjustable in
For the output of the actual speed value to the bus, the following conversion is made:
Note!
The scaling parameterisable via
is carried out as "Shift Operation". Overflows
are not absorbed!
Equation for scaling the speed setpoint
Parameter
Name
Description
Appl.: Reference speed
Reference variable for speed-related signals
ACDrive: Speed scaling
Scaling factor (-128 ... 127)
• In the Lenze setting "0", no scaling takes place (2
0
= 1)
Arithmetic example
Assumption:
• Reference speed (
) = 2000 rpm
• Speed setpoint selection via bus = 500 rpm (≡ 25 % of the reference speed)
Conversion of the internal scaling (16384 ≡ 100 %) in percentage:
Equation for scaling the actual speed value
Parameter
Name
Description
Appl.: Reference speed
Reference variable for speed-related signals
ACDrive: Speed scaling
Scaling factor (-128 ... 127)
• In the Lenze setting "0", no scaling takes place (2
0
= 1)
Speed setpoint
Application
Speed setpoint
Bus
[rpm]
16384
Reference speed [rpm]
----------------------------------------------------------
1
2
Scaling factor
--------------------------------
⋅
⋅
=
Speed setpoint
Application
500[rpm]
16384
2000 [rpm]
----------------------------- 1
2
0
------
⋅
⋅
4096
=
=
4096 100 [%]
16384
-------------------
⋅
25 [%] (of C00011)
=
Actual speed value
Bus
[rpm]
Actual speed value
Application
Reference speed [rpm]
16384
----------------------------------------------------------
2
Scaling factor
⋅
⋅
=