3 parameterising the motor control, Parameterising the motor control, 3commissioning – Lenze 8400 motec User Manual
Page 37

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
37
3
Commissioning
3.5
Commissioning of the "Actuating drive speed" technology application
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3.5.3
Parameterising the motor control
1. Select the Application parameters tab from the Workspace.
• The motor control parameters, among other things, can be found on the left:
2. In the Motor control list field (
), select the desired motor control.
3. Adapt the motor control parameters:
Note!
In the Lenze setting, the V/f characteristic control (VFCplus) with linear characteristic is
as motor control.
• V/f characteristic control (VFCplus) is a motor control mode for classic frequency
inverter applications on the basis of a simple and robust control procedure for the
operation of machines with a linear or quadratic load torque characteristic (e.g. fans).
• The presettings of the parameters ensure that the controller is immediately ready for
operation and the motors works adequately without further parameterisation if a
controller and a 50 Hz asynchronous machine with matching performances are
assigned.
Parameter
Lenze setting
Info
Value Unit
V/f base frequency
(
50.0 Hz
Adapting the V/f base frequency ( 101)
Imax in motor mode
(
)
47.00 A
Optimising the Imax controller ( 103)
Vmin boost
(
)
0.0 %