5.14.7
Motor speed monitoring
This function extension is only available from version 04.00.00!
If the drive reaches the maximally permissible motor speed (
• The error response "Fault" occurs, i.e. the inverter is inhibited and the motor changes to torque-
free operation (coasts down).
• The error message "
" is entered into the logbook.
5.14.8
Encoder open-circuit monitoring
This function extension is available from version 02.00.00!
When does the open-circuit monitoring system respond?
The open-circuit monitoring will trigger if
• an open circuit occurs in the encoder cable.
• an extreme overload (e.g. blocked motor shaft) occurs during the start-up phase of the motor.
• highly dynamic reversion of the motor occurs.
Which measured values lead to an actuation of the open-circuit monitoring system?
The following measured values checked for plausibility lead to an actuation of the open-circuit
monitoring system:
1. If for a time > 0.2 s, the amount of deviation between the actual speed value and the speed
setpoint is higher than f = 40 Hz.
2. If for a time > 0.2 s, the detected actual speed value is f = 0 Hz or n = 0 rpm and the I
max
controller is active at the same time.
3. If for a time > 0.2 s, the injected frequency and the actual speed value have different signs and
the I
max
controller is active at the same time. This is usually the case if A/B tracks are mixed up.
Response to open circuit
• If the open-circuit monitoring is tripped:
is activated (Lenze setting: "Fault").
• The "
SD3: Open circuit - feedback system
" is entered into the Logbook.
• A setting of
= "0: No Reaction" deactivates the monitoring.
Related topics:
Note!
In the Lenze setting (
= "1: Fault"), open-circuit monitoring of the encoder is
activated!