C00034 | ainx: configuration, C00036 | dcb: current, C00039 | fixed setpoint x (l_nset_1 n-fix) – Lenze 8400 motec User Manual
Page 341: C00039/1, C00039/2, C00039/3, Is used a, C00036, Is injecte, C00034/1
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
341
11
Parameter reference
11.2
Parameter list | C00034
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00034
C00036
C00039
Parameter | Name:
C00034 | AINx: Configuration
Data type: UNSIGNED_8
Index: 24541
d
= 5FDD
h
Configuration of the analog input for current or voltage measurement
Selection list
Info
0 0...+10 V(-10V...+10V)
Input signal is voltage signal 0 V ... +10 V
• 0 V ... +10 V ≡ 0 % ... +100 %
1 0...+20mA
With external load resistor (250 Ohms):
Input signal is the current signal 0 mA ... 20 mA
• 0 mA ... 20 mA ≡ 0 % ... +100 %
2 4...+20mA
With external load resistor (250 Ohms):
Input signal is the current signal 4 mA ... 20 mA
• 4 mA ... 20 mA ≡ 0 % ... +100 %
• The current loop is monitored for open circuit
(I < 4 mA) by the device.
3 AIn1 - AIn2
Voltage difference (-10 V ... +10 V) between input AIn1
and input AIn2
• Selection is only sensible when using an
E84DGFCXxNx Communication Unit (no fieldbus;
extended terminal design).
Subcodes
Lenze setting
Info
C00034/1
0: 0...+10 V(-10V...+10V)
AIN1: Config.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00036 | DCB: Current
Data type: INTEGER_16
Index: 24539
d
= 5FDB
h
Braking current in [%] based on rated device current (
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
%
100.0 50.0 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00039 | Fixed setpoint x (L_NSet_1 n-Fix)
Data type: INTEGER_16
Index: 24536
d
= 5FD8
h
FB: Fixed speed setpoints (JOG values) for the setpoint generator
Setting range
(min. value | unit | max. value)
-199.9
%
199.9
Subcodes
Lenze setting
Info
C00039/1
40.0 %
Fixed setpoint 1
C00039/2
60.0 %
Fixed setpoint 2
C00039/3
80.0 %
Fixed setpoint 3
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100