C00937 | field-oriented motor currents, C00939 | ultimate motor current, C00965 | max. motor speed – Lenze 8400 motec User Manual
Page 404: C00939, This ensu, C00938, Ited via, To 30, C00937/1, C000937/1
![background image](/manuals/566305/404/background.png)
11
Parameter reference
11.2
Parameter list | C00937
404
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00937
C00938
C00939
C00965
Parameter | Name:
C00937 | Field-oriented motor currents
Data type: INTEGER_16
Index: 23638
d
= 5C56
h
From version 04.00.00
Field weakening for synchronous motors
Display range
(min. value | unit | max. value)
0.00
A
320.00
Subcodes
Info
C00937/1
Field-producing current
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00938 | PSM: Maximum motor current field weakening
Data type: UNSIGNED_16
Index: 23637
d
= 5C55
h
From version 04.00.00
Field weakening for synchronous motors
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
500.00 30.00 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00939 | Ultimate motor current
Data type: UNSIGNED_16
Index: 23636
d
= 5C54
h
From version 03.00.00
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
A
3000.0 3000.0 A
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00965 | Max. motor speed
Data type: UNSIGNED_16
Index: 23610
d
= 5C3A
h
From version 04.00.00
When the drive reaches the motor speed set here:
• The "Fault" error response takes place, i.e. the motor is shut down immediately.
• The error message "
" is entered into the logbook.
Setting range
(min. value | unit | max. value)
Lenze setting
50
rpm
9999 9999 rpm
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1