3
Commissioning
3.5
Commissioning of the "Actuating drive speed" technology application
34
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3.5
Commissioning of the "Actuating drive speed" technology application
[3-1]
Block diagram for wiring the commissioning example for the "Actuating drive speed" application
Commissioning steps
Find a description of the commissioning steps of the "Actuating drive speed" technology application
below.
Please observe the sequence of the steps in the following chapters and follow them through
carefully. This will help you to commission your controller quickly and as safely as possible:
Prepare controller for commissioning
Creating an »Engineer« project & going online
Parameterising the motor control
Saving parameter settings safe against mains failure
Enabling controller and selecting speed
Note!
Take all the necessary safety precautions before you carry out the following
commissioning steps and switch the device on!
Safety instructions with regard to commissioning
System constellation
AR
Reference voltage (10 V) for analog signals
AU
Speed setpoint selection (slider of setpoint potentiometer R)
• Scaling: 10 V ≡ 100 % ≡ 1500 rpm
1
(for a 4-pole motor)
GND
Ground potential (GND) for analog signals
RFR
Controller enable
DIAG
Diagnostic interface for connecting the USB diagnostic adapter
8400 motec
X61
X6
DIAG
U V W
DO1 24O GND
NO COM AR
AU GND
X3/X4
RFR DI1 DI2 DI3 DI4 DI5 DO1 24O GND
NO COM
M
3~
i
R
1k
... 10k
W
W