C00239 | Limitation of lower speed
Data type: INTEGER_16
Index: 24336
d
= 5F10
h
From version 04.01.00
Here, a minimum lower setpoint speed can be set if, for example, the setpoint for pumps and fans should not fall
below a certain value. This prevents, e.g. a volume flow to be fallen below the minimum threshold.
• Compared to the setting "Min. analog setpoint" (
), this setting is scaled in [rpm] and is thus
independent of the reference speed set in
.
• This parameter can be used if old 8200 motec projects are migrated to the 8400 motec.
• In the Lenze setting "-9999 rpm", no limitation is active.
Note:
• Stopping commands such as DC-injection braking, quick stop and RFG_0 are executed independently of this
setting. Switch them off if you want to activate this setting.
• The maximum current controller can reduce the output frequency to below the minimum speed set here.
Setting range
(min. value | unit | max. value)
Lenze setting
-9999
rpm
9999 -9999 rpm
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00241 | L_NSet_1: Hyst. NSet reached
Data type: INTEGER_16
Index: 24334
d
= 5F0E
h
From version 04.00.00
Hysteresis window for setting the "speed setpoint reached" status
• Related digital signal in selection list: "62: LA_NCtrl_bSpeedSetReached"
• The reset hysteresis is permanently 0.5 %.
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
100.00 0.50 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100