Temperature sensor, Actions, Rediscover – HP Integrity NonStop J-Series User Manual

Page 177: Redundant power scrub, Set physical location, Rediscover redundant power scrub

background image

An optional text string assigned to further identify the physical location of
the module.
This attribute is displayed only if a value is specified using the Set Physical
Location action.

Locator

For DC-powered Telco systems only.
Displays the system alarm panel (SAP) identifier for this hardware resource,
as specified through the Alarm Panel Identifier option within the

Set Physical

Location

action. This attribute is displayed only if a value is specied through

the action.

Alarm Panel Identifier

Temperature Sensor

The current temperature, in degrees Celsius (°C), inside the enclosure of the
module.

Current Value

Actions

Rediscover

Causes OSM to

refresh

and

reanalyze

all components within the module. Use this action in situations

such as:

OSM does not recognize a new CRU following a CRU replacement.

An alarm remains after the alarm condition has been fixed.

Redundant Power Scrub

Tests fault tolerance of the power environment within the module. If the results of the action indicate
a problem, check the Power State attribute of the individual CRUs to determine where the problem
lies.

This action is run automatically at 2:00 a.m. daily. It can also be performed manually at any time.
See note below for default value of the new Redundant Power Scrub test.

On T0682AAC and later, this OSM action is also supported on Telco systems.

NOTE:

A new version of Redundant Power Scrub is available in T0682 ABE and later. It provides

independent battery testing and an extended load test for the bulk power supplies. With this new
version, the action can take up to 25 minutes to complete. The new battery scrub is significantly
enhanced in its ability to detect weak or failed batteries. For systems with many old batteries (over
5 years old), the battery scrub might call out multiple batteries for replacement.

To use this new functionality, in addition to installing OSM T0682 ABE or later, you must:

Update all enclosures with a new PIB-to-PIB crossover cable (see FCO 44440).

Add "PowerScrubVersion = 3" parameter to your OSMCONF file.

The default test interval for this new version is 7 days instead of 24 hours.

For information on creating and using an OSMCONF file or changing default values for this or
other parameters, see the OSM Configuration Guide.

Set Physical Location

Allows you to assign these

Physical Location

attributes for the module:

Rack Name is a user-defined name for the rack containing the module. You can enter up to
15 alphanumeric characters.

Rack Offset allows you to display a numerical value representing the location of the module
within the rack. A valid integer (from 1 to 42) must be specified when performing the Set
Physical Location action, or the action will fail.

Module 177