Toggle bit value – Rockwell Automation 9323-S5500D A.I. SERIES MICROLOGIX 1000 AND PLC-500 SOFTW User Manual
Page 459

MicroLogix 1000 and PLC-500 A.I. Series Software Reference
19-28
Toggle Bit Value
You can toggle bit values (for both I/O and data table memory) using the bit toggle
function. Although the bit toggle feature is not a true force function, it can have a
similar use in testing your ladder logic. Conditions in the ladder program that write to
the output data table override the toggle function. This function acts on the data table
I/O image (see the diagrams under the
I/O Forcing
heading), and thus has no effect on
output addresses that are forced ON or OFF.
The bit toggle function is of little use on real I/O in run mode, because both inputs and
outputs are overwritten each program scan. (Toggling a bit is NOT the same as forcing
a bit.)
!
MicroLogix 1000 users: The controller will fault if you set an output bit ON (1) that
does not exist as an actual output point on the controller. See the information on
status bit S:0/8 in
Appendix A - Programming Reference for Packaged Controllers
in
the
Instruction Set Reference
for information on changing this response.
There are several ways to use the bit toggle function:
•
Through the I/O Module System Configuration screen.
•
By pressing [Shift-F5] on the Ladder Logic display while in Processor Emulation
Mode (or while online).
•
From the Custom Display screen. Refer to the section on Custom Display later in
this chapter.
•
From the Multipoint Monitor screen. Refer to the section on
Multipoint
Monitoring
in
Chapter 4 - Data Table Addressing and Editing
.
To use the bit toggle function from the I/O Module System Configuration screen:
1.
From the top level of the ladder editor, press
[F8]
Display
.
2.
Press
[F3]
Mon i/o
.