beautypg.com

Rockwell Automation 9323-S5500D A.I. SERIES MICROLOGIX 1000 AND PLC-500 SOFTW User Manual

Page 390

background image

MicroLogix 1000 and PLC-500 A.I. Series Software Reference

16-12

Parameter Description

RTS send Delay

(x 20 ms)

If you are using a half-duplex communication device, you
may need to delay sending a message after activating an
RTS (request to send) signal. Valid range is 0-65535.

Pre-send Time Delay

(x 1 ms)

If the Control Line is set to No Handshaking or Full Duplex,
this parameter is the amount of time the Master delays its
transmission after having received the last character from a
slave.

If the Control Line is set to Half-Duplex Without Constant
Carrier, then this parameter the amount of time between the
Master receiving the last character from a slave and
asserting RTS prior to transmitting.

Normal Polling Range Enter the low and high addresses to set the range for

normal polling when the Polling Mode is set to Standard.
Valid addresses are from 0 to 254. If you set the Low
parameter greater than the High parameter, that polling
range is disabled.

Normal Poll Group Size Enter the number of nodes in the normal polling group. This

is the number of active normal addresses that will be polled
between priority polls. Setting this to zero causes all active
normal stations to be polled between priority polls. Valid
range is 0-255.