Configuring Channel 1
You can change the configuration for Channel 1. It is generally simpler to do this
while online with the processor, however, it is possible to make changes to channel
configurations offline and download the new configurations as part of the ladder logic
project.
To configure Channel 1:
1.
Go online with the processor.
2.
Select
[F8]
Display
.
3.
Select
[F7]
chancFg
. This displays the channel configuration screen. (The screen
shown here is for a SLC 5/04 processor.)
4.
Use the arrow keys to move the highlight bar to the
System Mode Driver
field for
Channel 1.
5.
If you are using a SLC 5/03 processor, you can set the driver to
DH-485 Master
or
Shutdown
. If you are using a SLC 5/04 processor, you can set the driver to
DH+
or
Shutdown
. If the channel is
Shutdown
, press
[F9]
Select
to toggle the setting
back to
DH-485 Master
or
DH+
.