Troubleshooting and Diagnostics

19-21

The following screen demonstrates the effect of forced I/O:

On the first rung, the input address is forced on, causing the input bit in the data table

to turn on, thus causing the output for that rung to be true. Both instruction indicators

appear in reverse video.

On the second rung, although the output is forced ON, the instruction does not appear

in reverse video because the force is written directly to the output device, not to the data

table. The rung is not true so the output data table value is not on.

On the third rung, although SECOND_OUTPUT is forced ON, the data table value is

still OFF. Therefore, the output for the third rung (THIRD_OUTPUT) is not energized.

Entering Forces

You can program forces in several ways:

Position the cursor on an instruction in the ladder program which references a real

I/O address and press

[F7]

Force

, then

[F1]

oFf

,

[F2]

On

, or

[F3]

Remove

. (See

Force Current Bit

below.)

Edit the force table for inputs or outputs using a display similar to the monitor data

file screen. Forces may be enabled, disabled or removed. (See

Force Table

Monitor

on page

19-26

.)

ƒ

ƒ