7-212
IM WX101-01E
Range/Type (PV1, PV2, Remote)
Select the voltage range, thermocouple, and resistive temperature detector type.
VOLT: 20mV, 60mV, 200mV, 2V, 6V, 20V, or 50V
TC:
TypeK, TypeJ, TypeT, TypeB, TypeS, TypeR, TypeN, TypeE, TypeL, TypeU,
TypeW, PLATINEL, PR40-20, or WRe3-25
RTD:
JPt100 or Pt100
When [SCALE/1.5V] is set to [1.5V], [Range/Type] is set to [6V].
Span (PV1, PV2, Remote)
Specify the measurement span in EU.
Scale (PV1, PV2, Remote)
Specify the scale between –30000 and 30000. However, this is only valid when [SCALE/
1-5V] is set to [Scale].
Unit (PV1, PV2, Remote)
Specify the units.
Use a maximum of 6 characters.
Sqrt (PV1, PV2, Remote)
Select or clear the check box to turn the square root function ON or OFF.
When it is on, set [Low Cut] between 0.0 and 5.0.
Bias (PV1, Remote)
Select the check box to turn the bias ON.
When it is ON, specify a EU (–100 to 100%) value.
Filter (PV1, Remote)
Select the check box to use a filter.
When it is ON, set between 1 and 120.
Ratio setting (Remote)
Turn ON when applying the designated ratio to remote measurement input.
When it is ON, set between –30000 and 30000. Set the decimal point position in the
range of 0 to 4.
On Style 2 or earlier, set between 0.001 and 9.999.
PV Range (PV Range)
Enter the maximum value, minimum value, decimal place, and units.
Set the max. and min. values between –30000 and 30000 such that max. > min., and
max. - min. = 30000.
PV Switching (PV Range)
Set within the input range. When setting Method to T/C Range in the Control Setting
tab within the Setup tab’s internal loop item, or when setting Method to PVHigh, only
the upper limit is set. If you set Method to Signal, the PV Input Switching setting is not
available.
Note
When the PV/SP math function is ON, the input settings are entered using [Control input
channel] items under the [Setting] tab for each control input channel. For the setting procedure,
see page 7-178.