Setting the Recorder
7.8 Setting MV1000/MV2000
For RS-232
• Baud Rate
Select 1200, 2400, 4800, 9600, 19200, or 38400 (bps).
• Parity
Set the parity check method to Odd, Even, or None.
• Data length
Select 7 or 8 (bits). To output the data in binary format, select 8.
• Handshaking
Select Off:Off, XON:XON, XON:RS, or CS:RS.
• Address
For Modbus protocol, enter a value in the range of 1 to 99. For a general purpose
communication protocol, this value is not set.
• Protocol
Select [Normal] for a general purpose communication protocol, [MODBUS] for Modbus
slave, and [Master] for Modbus master.
If Modbus master is selected, Modbus master settings must be entered.
For RS-422/485
• Baud rate
Select 1200, 2400, 4800, 9600, 19200, or 38400 (bps).
• Data length
Select 7 or 8 (bits). To output the data in binary format, select 8.
• Parity
Set the parity check method to Odd, Even, or None.
• Handshaking
Not specified.
• Address
Select a number from 1 to 99.
• Protocol
This is the same as with the RS-232.
Modbus master
Click to display the channel selection screen
Modbus master settings are enabled when you set [Protocol] to [Master] under [Serial] -
[Serial] in the [Basic Setting] tab.