Page 258
6-28
Installation and Maintenance Volume
Octel Overture 200/300 Serenade 3.0
PB60014–01
Port Mapping Status
Use the
PRTMAP
command to display information about the assignment of message-server port numbers
to ports configured in each slot. This command also displays the assignment of each port to an integration
unit. At the @ prompt, type
PRTMAP
Enter
If the PBX type is ATT75, each port can be assigned to more than one integration unit. If the PBX type is
not ATT75, each port can be assigned to only one integration unit and is assigned a line-appearance
number for that integration unit.
If a port is assigned to an integration unit and that port has the COS attribute for nonintegration, Attribute
58 — DO NOT USE THIS PORT FOR INTEGRATION, this command prints
***
after the integration
information for the port. The discrepancy in the configuration must be resolved, either by removing the
COS attribute from the port or removing the port from all integration units.
The following is an example of the
PRTMAP
command without ATT75 assigned:
@PRTMAP
SYSTEM
INTEGRATION
LINE
PORT
SLOT
PORT
EXTN
SLOT/UNIT
APPEARANCE
ID= 0
1
1
1
1210
10/1
1
2
1
2
1211
10/1
2
3
1
3
1212
10/1
3
4
1
4
1213
10/1
4
ID= 0
5
2
1
125
10/1
5
The following is an example of the
PRTMAP
command with ATT75 assigned:
@PRTMAP
SYSTEM
INTEGRATION
PORT
SLOT
PORT
EXTN
SLOT/UNIT
ID= 0
1
1
1
121
10/1 10/2 11/1 11/2
2
1
2
122
10/1 10/2 11/1 11/2
3
1
3
123
10/1
4
1
4
124
10/2
ID= 0
5
2
1
125
10/2
Floppy-Disk-Drive Diagnostics
Use the floppy-disk-drive (FD) diagnostic command
TEST FLOPPY 1
to isolate faults to the diskette,
floppy-disk drive, or floppy-disk controller. To run this test, at the @ prompt, type
TE F 1
Enter