When all the calibration (or validation) patterns of which automatic execution is enabled are
completed, the operation mode changes to the stop mode in the stream specifi cation status.
Run
W7
W7
W8
S8
S7
S7
Time
Stream specification 1
Calibration 1
Stream specification 1
Start of automatic calibration
Pause
Stop
● In the case where a stop command is received during the run mode in the (automatic)
calibration/validation status [4E2]
The operation mode is immediately prepared to be changed from the run mode to the stop
mode in the calibration (or validation) status.
The operation mode changes to the stop mode in the previous measurement status when
the current measurement is completed.
Run
W7
W7
W8
S7
S7
Time
Stream sequence 1
Calibration 1
Stream sequence 1
Start of automatic calibration
Stop
Stop
[4E2]
Stop command
● In the case where a forced stop command is received during the run mode in the (manual)
calibration/validation status [4F2]
The operation mode is immediately changed to the stop mode in the previous measurement
status.
● In the case where a forced stop command is received when the operation mode is prepared
to be changed from the run mode to the stop mode in the (manual) calibration/validation
status [4F3]
The operation mode is immediately changed to the stop mode in the previous measurement
status.
Stop
Stop
Run
(Waiting for stop)
W7
W7
S7
S7
Time
Stream sequence 1
Calibration 1
Stream sequence 1
Forced stop command
Start of automatic calibration
[4F2] [4F3]
(Stop command)