Yokogawa GC8000 Process Gas Chromatograph User Manual
Page 79

<1. Overview>
1-52
IM 11B08A01-01E
Run
W1
W1
S1
S1
[2F2]
Time
Stream specification 1
Forced stop command
Stop
● In the case where a forced stop command is received while the operation mode is
scheduled to be changed to the stop mode or pause mode in the stream specifi cation status
[2F3], [2F4]
The operation mode is immediately changed to the stop mode in the stream specifi cation
status.
In the stream specifi cation status (for N times of measurement), the number of times of
measurement is counted again from the beginning.
Run
(Waiting for stop or pause)
W1
W1
S1
S1
[2F3] [2F4]
Time
Stream specification 1
Forced stop command
Stop
● In the case where a forced stop command is received during the pause mode in the stream
specifi cation status [2F6]
The operation mode is immediately changed to the stop mode in the stream specifi cation
status.
In the stream specifi cation status (for N times of measurement), the number of times of
measurement is counted again from the beginning.
Pause
[2F6]
Time
Stream specification 1
Forced stop command
Stop
● In the case where a pause command is received during the stop mode in the stream
specifi cation status [2H1]
The operation mode is immediately changed to the pause mode in the stream specifi cation
status.
Stop
[2H1]
Time
Stream specification 1
Pause command
Pause
2nd Edition : May 11, 2012-00