2 interference suppression filters, Table 4.10.1.1: ac input choke – GE Industrial Solutions DV-300 DC Drive Users Manual User Manual
Page 74

GEI-100332Ga
——— WIRING PROCEDURES ———
4
30
Table 4.10.1.1: AC input choke
Converter
Main three-phase inductance
Rated
choke [mH]
Rated ac
current [A]
Saturation
current [A]
Freq. [Hz]
Model No.
Main 400 V, 3Ph, 50 Hz
6KDV3020Q2A.../Q4E...
1,71
17,2
34,4
50
KLR18CTB
6KDV3040Q2A.../Q4E...
0,855
34,4
68,8
50
KLR45CTB
6KDV3070Q2A.../Q4E...
0,488
60,2
120,4
50
KLR80CTB
6KDV3110Q2A.../Q4E...
0,311
94,6
189,2
50
KLR110CCB
6KDV3140.Q2A.../Q4E...
0,244
120,4
240,8
50
KLR160CCB
6KDV3185Q2A.../Q4E...
0,185
159
318
50
KLR300CCB
6KDV3280Q2A.../Q4E...
0,122
241
482
50
KLR300CCB
6KDV3350Q2A.../Q4E...
0,098
301
602
50
KLR360CCB
6KDV3420Q2A.../Q4E...
0,081
361
722
50
KLR420CCB
6KDV3500Q2A.../Q4E....
0,068
430
860
50
KLR600CCB
6KDV3650Q2A.../Q4E....
0,053
559
1118
50
KLR750CCB
6KDV3770Q2A.../Q4E....
0,044
662
1324
50
KLR750CCB
6KDV310HQ2A.../Q4E....
0,034
860
1720
50
KLR1250C
6KDV310HQ2A.../Q4E...
0,033
903
1806
50
KLR1250C
Main 460 V, 3Ph, 60 Hz
6KDV3017Q2B.../Q4F...
1,933
14,6
29,2
60
KLR18CTB
6KDV3035Q2B.../Q4F...
0,938
30,1
60,2
60
KLR45CTB
6KDV3056Q2B.../Q4F...
0,586
48,2
96,4
60
KLR80CTB
6KDV3088Q2B.../Q4F...
0,373
75,8
151,6
60
KLR110CCB
6KDV3112.Q2B.../Q4F...
0,293
96,4
193
60
KLR160CCB
6KDV3148Q2B.../Q4F...
0,227
127,4
255
60
KLR160CCB
6KDV3224Q2B.../Q4F...
0,146
193
386
60
KLR300CCB
6KDV3280Q2B.../Q4F...
0,117
241
482
60
KLR300CCB
6KDV3336Q2B.../Q4F...
0,098
289
578
60
KLR360CCB
6KDV3400Q2B.../Q4F....
0,082
344
688
60
KLR420CCB
6KDV3450Q2B.../Q4F....
0,073
387
774
60
KLR600CCB
6KDV3560Q2B.../Q4F....
0,058
482
964
60
KLR600CCB
6KDV3800Q2B.../Q4F....
0,041
689
1378
60
KLR1250C
6KDV3850Q2B.../Q4F...
0,038
732
1464
60
KLR1250C
GD0330g
4.10.2 Interference suppression filters
The converters of DV-300 series must be equipped with an external EMI filter in order to reduce the radio-
frequency emissions on the mains line. The filter selection is depending on the drive size and the installation
environment. For this purpose see the “EMC Guidelines”.
In the Guide it is also indicated how to install the cabinet (connection of filter and mains reactors, cable shields,
grounding, etc.), in order to make it EMC compliant according the EMC Directive 89/336/EEC.
The document describes the present situation concerning the EMC standards and the compliance tests made on
the GE drives.