GEI-100332Ga
——— WIRING PROCEDURES ———
4
8
Table 4.4.4: Jumpers on the R-TPD32-GE card
Designation
Function
Factory
S4
Matching of the input voltage of the tachogenerator reaction,
see table 4.4.3
S5,S6
Adaptation of the speed feedback type:
B
Pos. A
Sinusoidal encoder
Pos. B
Tachogenerator
Any position: digital encoder, armature feedback
S9
Adaptation to the signal of the analog input Input 1 (terminals 1 and 2)
OFF
ON
0 ... 20 mA / 4 ... 20 mA
OFF
0 ... 10V / -10 ... +10V
S10
Adaptation to the signal of the analog input Input 2 (terminal 3 and 4)
OFF
ON
0 ... 20 mA / 4 ... 20 mA
OFF
0 ... 10V / -10 ... +10V
S11
Adaptation to the signal of the analog Input 3 (terminals 5 and 6)
OFF
ON
0 ... 20 mA / 4 ... 20 mA
OFF
0 ... 10V / -10 ... +10V
S12 / S13
Terminating resistor for the serial interface RS485
OFF
ON
Interface terminated with resistor
OFF
Interface not terminated
S14
Field current resistors setting, see table 2.4.3.2
S15
Adaptation of the regulation card to the device type, see table 4.4.2
S18 / S19
Selection of the internal/external supply of the RS485 serial interface
OFF
OFF
Serial interface supplied from the outside (PIN 5 and 9) and
galvanic divided form the regulation section.
ON
Serial interface supplied from the inside and connected to the
potential reference point of the regulation. PIN 5 and 9 are used to
supply the adaptor of the serial interface (for use of 6KDV300PIU).
S20
Monitoring of the C channel of the digitall encoder on connector XE2
OFF
ON
C-channel monitored
OFF
C-channel not monitored
S21 / S22 / S23
Encoder supply voltage selection
OFF
ON
5 V encoder supply voltage
OFF
15...30 V encoder supply voltage
GD0160g
ON Mounted Jumpers
OFF Non mounted Jumpers
Table 4.4.5: Test points on Regulator card
Designation
Function
Designation
Function
XY20
Monitoring (± 10VDC) of the Se-
lect output parameters setting.
(Using this test point set all the Select output
1,2,3,4 to the variable that has to be measured).
XY17
Output current signal
(0.61 V =Nominal Drive output current)
XY10
Reference point
XY18
Reference point
GD0165g