GE Industrial Solutions DV-300 DC Drive Users Manual User Manual
Page 51

DV-300 Adjustable Speed Drives
——— WIRING PROCEDURES ———
4
7
Table 4.4.2: Dip-switch S15 adaptation of the regulation card to the device type
European
S15-1
S15-2
S15-3
S15-4
S15-5
S15-6
S15-7
S15-8
6KDV3020...
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
6KDV3040...
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
6KDV3070...
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
6KDV3110...
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
6KDV3140...
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
6KDV3185...
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
6KDV3280...
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
6KDV3350...
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
6KDV3420...
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
6KDV3500...
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
6KDV3650...
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
6KDV3770...
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
6KDV310HQ2...
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
6KDV310HQ4...
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
GD0150ag
American
S15-1
S15-2
S15-3
S15-4
S15-5
S15-6
S15-7
S15-8
6KDV3017...
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
6KDV3035...
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
6KDV3056...
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
6KDV3088...
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
6KDV3112...
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
6KDV3148...
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
6KDV3224...
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
6KDV3280...
ON
ON
ON
OFF
OFF
OFF
ON
OFF
6KDV3336...
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
6KDV3400...
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
6KDV3450...
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
6KDV3560...
ON
ON
OFF
ON
OFF
OFF
ON
OFF
6KDV3800...
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
6KDV3850
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
GD0150bg
Table 4.4.3 : Dip-switch S4 adaptation of the tachometer feedback to the input voltage
Tacho voltage
S4-1
S4-2
S4-3
S4-4
full scale (V)
S4-8
S4-7
S4-6
S4-5
22.7
ON
ON
ON
ON
45.4
ON
ON
ON
OFF
90.7
ON
ON
OFF
OFF
181.6
ON
OFF
OFF
OFF
302.9
OFF
OFF
OFF
OFF
DV0033g