DV-300 Adjustable Speed Drives

——— TROUBLESHOOTING ———

8

3

FAILURE ALARM POSSIBLE CAUSES

Overcurrent

Overcurrent in the motor circuit

Short-circuit or ground fault at the output of the converter

Current regulator optimized incorrectly

Overcurrent thr parameter too low

Field loss

Too low field current

The field regulation is blocked

The conductors in the field circuit are interrupted

Field fuses are active

Delta frequency

Excessive difference between the frequency of the three-phase power supply input and

the value measured the instant this is guaranteed.

Delta freq thres parameter set too low.

Check that the frequency of the three-phase power supply remains constant or in any

case within the threshold limit throughout drive operation.

Speed fbk loss

No speed feedback signal

The conductors of the feedback signal are interrupted

One or several encoder channels are missing (conductor interruption, no encoder power

supply)

Opt2 failure

Failure on the option card 2

Try a RESET. If you are still unsuccessful: probable internal fault. Contact your sales

office

Bus loss

Failure in the Bus connection (only with interface Bus option card)

Check the Bus connection

EMC compatibility problems

Try a RESET. If you are still unsuccessful: probable internal fault. Contact your sales

office

Hw opt1 failure

Failure on the option card 1

Try a RESET. If you are still unsuccessful: probable internal fault. Contact your

sales office