GE Industrial Solutions CAR2512FP Front-End User Manual
Car2512fp front-end, Data sheet, Input: 90v
![background image](/manuals/294751/1/background.png)
GE
Data Sheet
April 23, 2013
©2013 General Electric Company. All rights reserved.
CAR2512FP Front-End
Input: 90V
AC
to 264V
AC
; Output: 12V
DC
@ 2500W; 3.3V
DC
or 5 V
DC
@ 1A
Features
Universal input with PFC
Constant power characteristic
2 front panel LEDs: 1-input;2-[output, fault, over temp]
Remote ON/OFF control of the 12V
DC
output
Remote sense on the 12V
DC
output
No minimum load requirements
Active load sharing (single wire)
Hot Plug-ability
Efficiency: typically 92.5% @ 50% load
and 90.0% @ 20% load
Standby orderable either as 3.3V
DC
or 5V
DC
Auto recoverable OC & OT protection
Operating temperature: -10 - 70C (de-rated above 50C)
Digital status & control: I
2
C and PMBus serial bus
EN/IEC/UL60950-1 2
nd
edition; UL, CSA and VDE
EMI: class A FCC docket 20780 part 15, EN55022
Meets EN6100 immunity and transient standards
Shock & vibration: NEBS GR-63-CORE, level 3
Applications
12V
DC
distributed power architectures
Datacom, Telecom and ATE Equipment
Mid to high-end Servers
Enterprise Networking
Network Attached Storage
Routers/Switches/Access Nodes
Broadband Switches
Description
The CAR2512FP Front-End provides highly efficient isolated power from worldwide input mains in a compact 1U
industry standard form factor in an unprecedented power density of 25W/in
3
. It is ideal for datacom applications
such as enterprise networking, mid to high-end servers, and storage equipment, where mid to light load efficiency is
of key importance given the nature of the power consumption of the end application.
The high-density, front-to-back airflow is designed for minimal space utilization and is highly expandable for future
growth. The industry standard PMBus compliant I
2
C communications buss offers a full range of control and
monitoring capabilities. The SMBAlert signal pin alerts customers automatically of any state change within the power
supply.
*
UL is a registered trademark of Underwriters Laboratories, Inc.
†
CSA is a registered trademark of Canadian Standards Association.
‡
VDE is a trademark of Verband Deutscher Elektrotechniker e.V.
§
Intended for integration into end-user equipment. All the required procedures for CE marking of end-user equipment should be followed. (The CE mark is placed on selected products.)
** ISO is a registered trademark of the International Organization of Standards.
+ PMBus name and logo are registered trademarks of the System Management Interface Forum (SMIF)
RoHS Compliant