DV-300 Adjustable Speed Drives
——— FUNCTION DESCRIPTION ———
6
185
6.17.2.2 Taper function
OPTIONS
Torque winder
Torque calculat
Taper function
[1176]
Taper enable
[1177]
Init diameter [m]
[1178]
Final diameter [m]
[1180]
Tension ref [%]
[1179]
Tension red [%]
[1194]
Act tension ref [%]
Parameter description
No.
Value
Standard
Configuration
min
max
Factory
American
Factory
European
Taper enable
Enabled (1) / Disabled (0)
1176
0
1
Disabled (0)
Disabled (0)
*
Init diameter [m]
1177
0.000
32.000
0.1
0.1
Final diameter [m]
1178
0.000
32.000
1
1
Tension ref [%]
1180
0.00
199.99
0
0
**
Tension red [%]
1179
0.00
199.99
0
0
**
Act tension ref [%]
1194
0.00
200.00
0
0
***
*
This parameter can be set on a programmable digital input.
** This parameter can be set on a programmable analog input.
*** This parameter can be set on a programmable analog output.
Tension ref
Min
diameter
Max
diameter
Init
diameter
Final
diameter
Tension ref x 1 -
Tension red
100
Roll diameter
Act tension ref
Figure 6.17.2: Relation among the Taper function parameters
Taper enable
Enabling of Taper function.
Init diameter
Diameter for the starting of the taper tension reduction in meters.
Final diameter
Diameter for the ending of the taper tension reduction in meters.
Tension ref
Tension reference in %.
Tension red
Taper tension reduction as a percentage of Tension ref.
Act tension ref
Monitor for the active tension reference as a percentage of Tension ref.